15 - 38 kV HV Capacitor Bank - Power factor switching |
![]() |
The VersaVac (VSV) is a long life vacuum switch used for pole top Capacitor switching. The VSV was specifically designed to replace oil switches to eliminate costly maintenance. The VSV can be used as a
direct replacement on existing banks or supplied by manufacturers on new
banks. Joslyn's unique design incorporates Joslyteä , the field proven
solid dielectric foam that has been successfully used over 35 years. ![]() |
![]() |
Specifications |
|||
Voltage Class (kV) | 15 | 27 | 38 |
Maximum Voltage | |||
- Solid Grounded Applications (kV) | 15.5 | 27.5 | 38 |
- ngrounded Applications (kV) | 15.5 | 27.5 | N/A |
- ngrounded Applications with Manual Trip (kV) | 12.47 | 22.5 | N/A |
Impulse Withstand (kV BIL) | |||
- Line to Ground | 95 | 125 | 150 |
- Open-Gap | 95 | 95/125 | 125 |
Power Frequency AC Withstand Dry/Wet (kV RMS) | 36/60 | 60/50 | 70/60 |
Units equipped with manual trip handle. |
Application | Grounded or Ungrounded | |
General | Style | VerSaVac Single-Phase Distribution Switch |
Material | Porcelain / Epoxy | |
Dimension Information | Interrupter Module Assembly Height Inches (MM) | 18 (457.2) |
Terminal to Terminal Height Inches (MM) | 8 15/16 (227.0) | |
Total Height Inches (MM) | 27 5/8 (701.7) | |
Specifications | Weight LBS. (KG) | 30.8 (14.0) |
Number of Pins in Connector | 5 | |
Ratings | Exceeds Electrical Requirements of ANSI C37.66 | |
Continuous Current | 200A | |
Short-Time Current | 6kA (1/2 sec.), 4.5kA (1 sec.) | |
Asymmetrical Momentary/Making Current | 9kA Asymmetrical RMS/23kA Peak | |
Peak Inrush Current Limit for Parallel or Back-to-Back Switching Applications | 6kA | |
Control Voltages | 120VAC, 240VAC | |
Minimum Operating Voltage | 80VAC, 160VAC | |
Recommended Control Pulse Time | 100 msec. | |
Auxiliary Contact Rating | 15A 120VAC, 0.5A 125VDC | |
Accessories | Junction Boxes, Cable Assemblies, Current Sensors, Mating Connectors, Animal Protectors (2 per switch), Undervoltage Trip Control, Zero Voltage Closing (ZVC) Control, 125 DC Control Interface |
[Print] [Top] [Request More Information] [Home] [Customer Links] |