| Basic Operating Parameters |
R~L-GSE |
| Rated Frequency |
50/60Hz |
| Rated cubicle (auxiliary) supply voltage |
85 to 265 V AC/DC |
| Rated operating sequence |
0-0.1s-C0-1s-C0-1s-C0-60s |
| Degree of protection |
IP54 |
| Temperature range |
-40°C to +55°C |
| Maximum humidity |
100 % |
| Maximum altitude above sea level |
2000 m |
| Vibration endurance (Pole mounted) |
IEC 60255-21-1 Class 1, test acceleration 1.5g |
| Vibration response (Pole mounted) |
IEC 60255-21-1 Class 2 |
| Shock response (Pole mounted) |
IEC 60255-21-2 Class 1 |
| Bump |
GOST 17516.1-90, class M7, GOST 16962.2-90 |
| Seismic |
IEC 60255-21-3 Class 1 |
| Operating time after loss of auxiliary supply , hours, not less: (Without providing power for RTU and USB, without IOM, CPM off) |
|
| - at +25°C |
48 |
| - at -40°C |
12 |
| - at +55°C |
48 |
| RTU power supply: |
|
| - voltage range |
5 to 15 V, step 0.5 V |
| - max output power |
15 w |
| - max output power at 0.5 duty cycle (range 12-15 V) |
30W |
| Maximum power consumption of RC from auxiliary supply |
60W |
| Weight |
29 kg (Battery, IOM and RTU not included) |
| Dimensions |
450x860x390 mm |