Specifications |
|
| Voltage | 11 , 22 or 33kV Continuous |
| Lightning Impulse | 210 Kv |
| Current | 600 amp single flexible continuous |
| Fault | 13.1kA for 1 second (33 kA peak) |
| Insulation/Insulator | |
| Power frequency Withstand Test Voltages | Power frequency – wet: 100kV, Lightning Impulse- Dry: 210kV |
| Creepage Distances | |
| Total creepage distance | 690mm |
| Protected creepage | 140mm |
| Flashover | 405mm |
| Minimum Failing Loads | |
| Cantilever | 1.8kN |
| Torsion | 300Nm |
| Tension | 25kN |
| Phase Centres | 1000mm and 1300mm standard or to requirement |
| Main Items | Twin Bolt (NEMA) terminals, tin plated Stainless steel flicker arc horns Silver Plated Cu contacts of V design Intermediate pipe guide for 25 NB pipe and bottom handle |
| Options | 600 amp load break heads with Kearney or Duo-gaps Earth points for live work Pole top mounting Raised feet 1.6m long equal spacing Dropout fuses |
FEATURES |
BENEFITS |
| Unitised Frame Design (Fully welded one-piece frame) |
Rigidity - Reduce flexing of switch frame providing reliable long term contact alignment. Ease of installation - Switch supplied fully assembled and factory set up for immediate installation and use. (Have been installed within 30 minutes). Ease of live line installation (one-piece lift). 6mm bearing surface to prevent seizing of moving parts. Structure steel is hot dipped, galvanised mild steel. |
| Customised Frame Design (Both Unitised and Demountable designs can be customised to customer requirements). |
Packaging – Fully assembled. Pole Spacing - Fully adjustable phase spacing. Set-up - Contact alignment is factory set. Operation - Square axle provides full adjustment of operating lever position relative to pole. Installation - Switch frame can be installed independently and switch poles mounted individually. |
| Frame Construction High Strength Spar (100x100x3mm) |
Range of options to date include : • Various spar lengths • Various spar mounting hole configurations • Various phase pole spacing • Special earthing tags • Special mounting feet/brackets • Lifting lugs • Extended axle • Vertical mount • Special handle design • Line strain point on end of pole base • Fuse mounting brackets Eliminates flexing due to pole movement or cross arm warping. Enables line termination through dead end mounted directly onto spar. Provides sufficient strength to enable ABS to be mounted directly to the pole as a cross-arm. |
| Pole Construction Strong Switch Pole Base (75x40mm) |
Eliminates the need to regularly re-adjust contact alignment. Strong enough to support line strain point or additional equipment mounting. |
| Factory Tested Design 2000+ Operations without re-adjustment of contact assemblies or bearing points) |
Proven long reliable switch life. |
| Insulator Construction | Ceramic New Zealand Manufactured |
Contact Assembly Construction |
|
| Materials | |
| Silver plated contacts Plate and Bronze castings Flexible conductor
|
Improved electrical performance. • 600A continuous rating with flicker arc breaks One piece plated bronze contact mounted casting bolted directly onto insulator. |
| Type Tested | Tested designs to IEC 129:1984 BS 5253:1990 Fault level 15 kA / 1 sec |
| Test Results | • Power Frequency 28/32kV • Thermal Rating 600A • Short Time Rating 250MVA for 1 second • Contacts are 25 micron Tin plated to prevent corrosion • Contacts are 5 micron Silver-plated |
| [Print] [Top] [Request More Information] [Home] [Customer Links] |
| © Copyright 2006-2012 Power Consultants Pty Limited. All rights reserved. |